200Smart与仪表的modbus通讯

仪表的功能码:0x03:读保持寄存器
0x04:读输入寄存器
仪表的输入寄存器地址 0x0001 温度值 2字节
0x0002 湿度值 2字节
Modscan32软件充当主站,用485线将仪表和电脑连接。

在MODSCSAN32软件中,配置—》显示选项—》显示数据流

注意:Modscan32软件与仪表通讯时,PLC就无法与仪表通信了,因为Modbus是
单主站通讯。Modscan32充当主站,PLC就无法当主站了。
由PLC作为主站跟仪表进行通讯:

当有多个Modbus仪表时,要修改仪表的设备号
当连接有多个Modbus仪表时,需要通过Modscan32软件修改每个仪表的设备号
然后再连入PLC进行通讯。

此时已把默认的站地址1改成了站地址2了。
MODBUS(客户端和服务端)指令的管脚定义


Modbus地址与S7-200Smart CPU地址映射关系